UPS backup time calculation
How backup time is actually calculated, and why the simple formula understates the truth.
The basic relationship
Backup time is the available battery energy divided by the load. In practice: battery capacity in ampere-hours multiplied by battery voltage gives watt-hours; multiply by the inverter efficiency and the depth of discharge you are prepared to use; divide by the load in watts.
Why the answer is optimistic
Battery capacity is rated at a specific discharge rate. At a fast discharge the delivered capacity is lower than the nameplate figure.
Capacity is rated at 25 °C. At 35 °C the available capacity is reduced and the service life falls sharply.
Capacity falls as the battery ages — a five-year-old battery does not deliver its original capacity.
The inverter is not perfectly efficient, and efficiency varies with load.
Loads rarely draw the figure on the label; measured load is usually different.
Doing it properly
Use the battery manufacturer’s discharge tables for the actual load and the target end voltage, then apply a temperature correction and an ageing allowance. That produces a figure you can rely on in the third year, not just on day one.
A practical approach
Send us the UPS model, the measured load and the autonomy you need. We will calculate the configuration from the discharge tables and state the assumptions.