ABB REF615 feeder protection relay
A feeder protection relay for medium-voltage switchgear, and what it protects against.
What a feeder protection relay does
It measures current and voltage on a feeder and trips the circuit breaker when it detects a fault condition. Unlike a low-voltage breaker with an integral trip unit, a relay is a separate device configured for the specific protection scheme the feeder requires.
Protection functions typically applied
Overcurrent and earth fault protection
Directional overcurrent where fault direction must be distinguished
Distance or differential protection on more complex feeders
Breaker failure protection
Under- and over-voltage, and frequency protection where relevant
Trip circuit supervision, so a broken trip coil is detected before it is needed
What the configuration depends on
The network earthing arrangement
Whether the feeder is a single source or part of a ring or parallel arrangement
The fault levels expected at that point
The coordination scheme with the relays upstream and downstream
The communication requirements for SCADA or substation automation
Commissioning
A relay installation is commissioned by injecting test currents and voltages, verifying each protection function and its trip time, and checking the trip circuit end to end. The settings are recorded and handed over.